Troubleshooting; Fault Condition Description And Operation - GE Fuji Electric AF-300ES Instructions Manual

1/2 - 350 horsepower
Table of Contents

Advertisement

Section 8: Troubleshooting
TABLE 11: Fault Condition Description and Operation
The following GE AF-300E$ drive protection functions have been incorporated in the basic drive software and will be
indicated in the LED display as well as listed in the fault table display.
Ground Fault
Grounded output. The protecction is effective for Drive output
terminals - U, V, W.
(Drive cannot protect against an input line overvoltage.)
Under voltage
Protects the Drive when the DC bus voltage reaches the
Over heat
Protects the Drive against overheating caused by
overload operation, cooling fan failure, abnormal high ambient
overload
Range of setting: 20 to 135% of Drive rated current.
Inside fuse
Detects the DC bus failed fuse, 15 Hp and above.
Keypad
Detects a continuous communication error between
communication
control PCB and keypad panel.
CPU error
Detection of a CPU malfunction.
Option
Detects a continuous communication error between
communication
control PCB and option PCB.
Option error
Detects Drive option failure.
Operating
Detects Drive operating procedure error during Drive startup.
Proc. Error
FWD or REV connected to terminal CM at time of main power
being applied to Drive. Stop keypad in remote operation.
Tuning error
Detects missing connection to the motor @ auto-tune.
Prevent
Prevents OC-trip by ceasing frequency output at high current when
stall
torque limit is disabled and drive is accelerating, or when high impact
loads are applied to the motor. Second, by decreasing frequency
level when torque limit is activated and its value is being exceeded
during steady state operation and load acceleration.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
8-1
LED
Alarm RY
Remarks
Display
(30A, B & C)
O C 1
At accel
O C 2
At decel
O C 3
At oper
EF
Grnd Fault
O U 1
At accel
O U 2
At decel
O U 3
At oper
L U
Function
10: 0 or 1
10: 2,3,4
O H 1
Fin temp.
O H 3
Internal
temp.
d b H
O L U
F U S
O H 2
E r 1
E r 2
E r 3
E r 4
E r 5
E r 6
E r 7
X
X
X
X
- no
X
X
X
X
X
X
X
X
X
X
X
X

Hide quick links:

Advertisement