Control Terminal Board 40 - 300 Hp
CAUTION
Remove Jumper from between terminals THR and CM
when thermal interlocks are used.
CAUTION
Remove jumper from between terminals FWD and CM.
NOTE
Wiring connections for operation with kaypad reference
control.
CM-FWD and CM-THR terminals are jumpered
together at the factory.
Power Terminal Boards
40-75 Hp
100 – 300 Hp
NOTE: A DC Link Reactor is also shipped for connection between terminals P1 - P+, 100 Hp and greater.
Figure 4-5. 40 - 300 Hp TERMINAL BOARDS
4-5