GE Fuji Electric AF-300ES Instructions Manual page 41

1/2 - 350 horsepower
Table of Contents

Advertisement

Table 5:
Terminal Identification/Function (continued)
Terminal
Terminal
Label
Name
Control Terminal Board Cont'd
HLD
3-wire Operation -
Stop Command
(Operation From
Momentary Contacts)
RST
Reset Signal Input
THR
External thermal trip
command
FMA
Frequency Meter
Connection Points
Analog
FMP
Frequency Meter
Connection Points
Pulse
AX1
Run Relay Dry
AX2
Contact Output
30A
Fault Relay Output
30B
Terminals
30C
X1-X5
Multi-step Input
Function Selection
Y1-Y5
Multi-step Output
Function Selection
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Function
When 3-wire operation is selected and HLD-CM is closed, the pulse
signal input from FWD, REV terminals is held internally.
After removal of fault condition, Faults are reset when a momentary
contact closure is made between the RST-CM terminals for more than
0.1 seconds.
NOTE: If there is an input to the FWD and/or REV terminals, the unit
will not RESET.
With THR-CM (open), OH2 trip will occur and the motor will
coast-to-stop.
NOTE: With no external thermal relay or external braking resistor
thermostat, the THR-CM terminals must be closed or the drive
will not operate. OH2 is a latched fault.
Provides an output of 0 to +10 VDC (+10Vdc at max. frequency.)
Available for connection of a voltmeter (with internal resistance of
10K ohms.) See Function Code 46 for monitoring selection. Meter
connects between terminal FMA & 11. Two (2) voltmeters, each having
an internal resistance of 10KΩ can be connected in parallel.
Pulse frequency output equal to drive output frequency multiplied
by the set value of Function Code 43. Meter connects between FMP
and CM.
Contact is closed when the drive is running. (Contact rating
resistive load: 250 VAC, 0.3 Amps.) (Only applicable to 40 Hp and greater)
During normal operation, the relay is not energized and contact is made
between 30B and 30C. When a fault is detected, the relay is energized
and contact is made between 30A and 30C. (Contact rating resistive
load: 250 VAC, 0.3 Amps.)
– Seven preset speed selection
– Increment/Decrement function
– DC Brake command
– 2nd motor selection
– Switching operation from ac line to Inverter
– Data protection
– Drive running
– Frequency equivalence signal
– Frequency level detection
– Pattern timing signal
– Overload early warning
– Under voltage detection
– Keypad operation
– Auto restart
– Auto reset
4-9