Technical data
This table shows the technical data. See also dimension illustration at page 38
Introduction
Specification
Operating range
Efficiency
Sound from cabinet 126 m3/h @ 70 Pa, Lw(A)
Sound from ducts 126 m3/h @ 70 Pa
Supply/Extract, Lw(A)
Filters According EN779:2012 (Exhaust/Supply)
Installation surrounding temp.
Maximum humidity in extract air @25°C
Outdoor temp (without preheating installed)
Outdoor temp (with preheating installed)
CABINET:
Dimensions WxHxD (without bracket)
Duct connectors
Weight
Insulation Lambda 0,031 W/mK
Drainage hose included
Cabinet colour
Fire classification, polystyrene DIN 4102-1
Fire classification, unit according EN 13501-1:2002
ELECTRICAL:
Power input (tolerance 10%)
Max. current consumption (without/with preheater* )
Frequency (tolerance 2%)
IP-class
*Accesory
32
Unit
Data
m3/h
50 to 220
85
dB(A)
dB(A)
54/43
G4/G4
Class
(F7 option)
°C
+12 to +40
RH%
65
°C
-12 to +50
°C
-25 to +50
mm
600x1122x279
mm
Ø125 - female
kg
34
W/(m*K)
U<1
ø/length
1/2" – 2m
RAL
9016
Class
B2
Class
E
V AC
230
Watt
127 / 1196
Hz
50
IP class
20