Installation options, continued
Location and duct
connections
10
The following should be considered selecting an appropriate location for installation:
1. Please ensure that the ceiling or walls structure is adequate to withstand the unit addi-
tional weight.
2. It is mandatory to tilt the HCC2 Alu minimum 1° towards the drain. The enclosed bracket
will automatically provide this requirement.
3. The HCC2 Alu units, is designed to mounted in dry surroundings, with temperatures
>12°C. Utility room or similar heated rooms.
4. The air flow direction can be electronically swapped, providing ability to route the con-
nected ducts, either to the right or to the left. See more about swapping at page 11.