Mitsubishi Q Series User Manual page 81

Loop control module
Hide thumbs Also See for Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS
Address
(Decimal (Hexadecimal))
CH1
CH2
51(33
)
83(53
)
MAN output setting
H
H
52(34
)
84(54
)
Setting change rate limiter
H
H
53(35
)
85(55
)
AT bias
H
H
Forward/reverse action setting
54(36
)
86(56
)
H
H
55(37
)
87(57
)
Upper setting limiter
H
H
56(38
)
88(58
)
Lower setting limiter
H
H
57(39
)
89(59
)
Program control run/reset
H
H
Loop disconnection detection
59(3B
)
91(5B
)
H
H
judgement time
Loop disconnection detection
60(3C
)
92(5C
)
H
H
dead band
61(3D
)
93(5D
)
Unused channel setting
H
H
PID constant read command from
62(3E
)
94(5E
)
H
H
FeRAM
Automatic backup setting after
63(3F
)
95(5F
)
H
H
auto tuning of PID constants
164(A4
)
Alert dead band setting
H
165(A5
)
Alert delay count
H
167(A7
)
Approach range setting
H
168(A8
)
Approach soak time criteria
H
169(A9
)
PID continuation flag
H
176(B0
)
Cascade ON/OFF
H
177(B1
)
Cascade gain
H
178(B2
)
Cascade bias
H
179(B3
)
Cascade monitor
H
192(C0
)
208(D0
)
Mode setting of Alert 1
H
H
193(C1
)
209(D1
)
Mode setting of Alert 2
H
H
194(C2
)
210(D2
)
Mode setting of Alert 3
H
H
195(C3
)
211(D3
)
Mode setting of Alert 4
H
H
3 - 50
Settings
*1: Reading is always available regardless of the write conditions. The item of which write condition is set to
"Setting mode" is changeable on setting mode only. Note that changing items during the operation
mode causes a write data error. In addition, it is necessary to turn on the setting change command
(YnB) for changing the setting.
Range
Manual
-50 to 1050
control 1
( 0.1%)
Manual
0 to 4000
control 2
Thermocouples
1 to 10000
( )
( 0.1 /min)
Micro voltage
(mV), voltage
0 to 1000
(V), current
( 0.1%/min)
input (mA)
full-scale
0: Forward action, 1: Reverse
action
Input range
0: RESET, 1: RUN
0 to 7200 (s)
0 to full-scale
0: Used, 1: Unused
0: Without, 1: With command
0: OFF, 1: ON
Thermocouples
0 to 1000
( )
( 0.1 )
Micro voltage
(mV), voltage
0 to 1000
(V), current
( 0.01%)
input (mA)
0 to 255
Thermocouples
0 to 100
( )
( 0.1 )
Micro voltage
(mV), voltage
0 to 100
(V), current
( 0.1%)
input (mA)
0 to 32767 ( 0.1s)
0:Stop, 1:Continue
0: OFF, 1: ON
-10000 to 10000 ( 0.001)
-1000 to 1000 ( 0.1%)
0 to 14
MELSEC-Q
(From previous page)
Write condition *1
Default
Setting
value
Always
mode
-50
0
0
1
13720
-2000
0
80
0
0
0
0
5
0
1
0
0
0
1000
0
0
(To next page)
Disabled
3 - 50