3 SPECIFICATIONS
Set value
Wait status flag
(Buffer memory address: 261, 517)
3 - 93
(4)
Pattern end output time of program pattern
(a) This setting sets the time of the pattern end output at the completion of the
program pattern.
The default value is 0.
(b) Q62HLC, when the program pattern is completed, keep the set value at the
pattern end and continues the PID control only for the pattern end output
time.
Set value
(c) The setting range is 0 to 30000.
When 0 is set, however, the output of pattern end continues until the
program control is reset.
(d) The time scale is set by the time scale (buffer memory address: 274, 530).
(e) When the program pattern has been linked, the program pattern setting,
which is specified at the execution pattern setting (buffer memory address:
272, 528), is valid.
(5)
Wait zone of program pattern
(a) If the measured value cannot reach the set value after the set time of the
segment has passed, this setting sets a zone for the program to wait for
shifting to the next segment.
(b) By setting the wait zone, the Q62HLC stops the progress of the program
control per segment, and waits for moving to the next segment until the
measured value reaches the range of the wait zone. (Wait status)
Segment 1
Wait status
0
Output time of pattern end
Start of segment 2
Measured value
Segment 2
1
Pattern end
Operation completed
0
MELSEC-Q
Time
Wait zone
Time
3 - 93