Mitsubishi Q Series User Manual page 33

Loop control module
Hide thumbs Also See for Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS
Table 3.1 Q62HLC performance specification list (from previous page)
Item
Control method
PID constant
PID constant
range
setting
Proportional
band (P)
Integral time (I) 0.0 to 3276.7s
Derivative time
(D)
Set value setting range
Dead band setting range
Time accuracy
Noise immunity
Insulation
FeRAM read/write count
Number of occupied I/O points
Connection terminal
Applicable wire size
Applicable crimping terminal
External power supply
Internal current consumption
Weight
External dimension
2: For the noise immunity, dielectric withstand voltage, insulation resistance and others of the programmable controller system which
uses this module, refer to the power supply module specifications given in the User's Manual of the CPU module used.
3 - 2
Continuous proportional control
Auto tuning setting available
Thermocouple: 0.1 to Full-scale
Micro voltage, Voltage, Current: 0.1 to 1000.0%
0.0 to 3276.7s
Thermocouple: Input range of the thermocouple to be used
Micro voltage, Voltage, Current: Set input range
Thermocouple: 0.0 to 100.0
Micro voltage, Voltage, Current: 0.00 to 10.00%
0.2%
Insulation part
Insulation method
Between input and
earth
Between input
channels
16 points/slot (I/O assignment: 16 intelligent points)
Specifications
*2
Dielectric withstand
voltage
Transformer
insulation
500VAC for 1 minute
Transformer
insulation
10
Max. 10
times
18-point terminal block
2
0.3 to 0.75mm
R1.25-3, RAV1.25-3
24 VDC +20%, -15%
Ripple, spike 500mV
or less
P-P
Inrush current: 0.2A, 4ms or less
0.07A
0.27A
0.25kg
27.4 (W) 98(H) 112(D)mm
MELSEC-Q
Insulation resistance
500VDC 20M
or
more
3 - 2
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q62hlcSw0d5c-qtcu-eSw0d5c-qtcu-ea

Table of Contents