(c) The wait zone is set to the zone where the setting value of the wait zone is
divided into the plus side and the minus side for the set value.
For example, in the case where the set value is 100
of the wait zone is 10 , the actual wait zone will be 90 to 110 .
(d) If turning on the command advancing (buffer memory address: 202, 218) in
wait status, this setting cancels the wait status and executes the control
from the next segment after performing the advancing operation.
(e) The setting range is 0 to full-scale.
However, when 0 is set, it will be "No wait zone".
(f) When the program pattern has been linked, the wait zone of the executing
program pattern is valid for the wait zone.
(g) Whether it is in wait status or not is confirmed by the wait status flag (buffer
memory address: 261,517).
(6) Segment set value (SV) setting
(a) This setting sets the set value of the segment 1 to 16.
The default value is 0.
(b) The setting range is within the input range.
(7) Segment time scale
(a) This setting sets the time scale (execution time) of the segment 1 to 16.
The default value is 0.
(b) The time scale is set by the time scale (buffer memory address: 274, 530).
(c) The setting range is 0 to 30000.
(8) Segment Zone PID data No.
(a) This setting selects the zone PID data to be used in segment 1 to 16.
The default value is 0.
(b) The setting range is 0 to 8.
When 0 is set, however, the zone PID data of the zone including the current
set value is automatically selected.