6 PROGRAMMING
6 - 24
(2) Operating the utility package
(a) Initial setting (Refer to Section 5.4)
<When cascade control is not executed>
CH1 Input Range ......................................................"0"
CH2 Unused Channel Setting .................................."Not Used"
[Limiter setting]
CH1 Upper Setting Limiter ......................................."2000"
CH1 Lower Setting Limiter ......................................."0"
[Alert function setting]
CH1 Alert 1 Mode Setting........................................."UprLmt Input"
CH1 Alert Set Value 1 .............................................."1800"
[Normal control setting]
CH1 Set value (SV) setting ......................................"800"
[Program control setting]
CH1 Execution Pattern ............................................."Program Pattern 1"
CH1 Time Scale........................................................"1s"
CH1 Program Pattern 1
Final Segment.................................................."4"
Segment 1 Set Value (SV) setting .................."1500"
Segment 1 Executing Time ............................."200"
Segment 1 Zone PID data No. ........................"2"
Segment 2 Set Value (SV) setting .................."1500"
Segment 2 Executing Time ............................."100"
Segment 2 Zone PID data No. ......................."2"
Segment 3 Set Value (SV) setting .................."500"
Segment 3 Executing Time ............................."100"
Segment 3 Zone PID data No. ........................"1"
Segment 4 Set Value (SV) setting .................."500"
Segment 4 Executing Time ............................."100"
Segment 4 Zone PID data No. ......................."1"
<When cascade control is executed>
CH1 Input Range ......................................................"0"
CH2 Input Range ......................................................"0"
CH1 Unused Channel Setting .................................."Used"
CH2 Unused Channel Setting .................................."Used"
[Limiter setting]
CH1 Upper Setting Limiter ......................................."2000"
CH1 Lower Setting Limiter ......................................."0"
CH2 Upper Setting Limiter ......................................."2000"
CH2 Lower Setting Limiter ......................................."0"
[Normal control setting]
CH1 Set value (SV) setting ......................................"1000"