Detail: When ON, Cause the PID controller to be bypassed and sets PWM parameters for the IMV with a
constant duty cycle defined by IMV_ManualDC.
IMV_ManualDC
Tip Strip: Value to override IMV PID final output when ManualOverride=TRUE
Units: %
Detail: Manual duty cycle applied to IMV when
IMV_MaxDCCalc
Tip Strip: Maximum allowed duty cycle for IMV based on battery voltage and nominal solenoid resistance to
limit current to 3A for channel pair
Units: %
Detail: Maximum duty cycle limit based on the battery voltage and the nominal resistance of the valve. This
value prevents the current from exceeding the limitations of the LS channels driving the IMV solenoid.
IMV_MaxDC
Tip Strip: Maximum allowed duty cycle for IMV. This value is effective if lower than IMV_MaxDCCalc.
Units: %
Detail: Maximum allowed duty cycle for IMV. This value is effective if lower than IMV_MaxDCCalc.
IMV_MinDC
Tip Strip: Minimum allowed duty cycle for IMV.
Units: %
Detail: Minimum allowed duty cycle for IMV.
IMV_DC
Tip Strip: Final IMV duty cycle
Units: %
Detail: Final duty cycle applied to the IMV solenoid.
166 | ni.com | NI DIDS-2100 Series User Manual
IMV_ManualOverride
is on.