Dnp Communications; Device Profile Document - GE Feeder Management Relay 750 Instruction Manual

Table of Contents

Advertisement

7 COMMUNICATIONS

7.5DNP COMMUNICATIONS

DNP 3.0

DEVICE PROFILE DOCUMENT

Vendor Name: General Electric Multilin Inc.
Device Name: 750/760 Feeder Management Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is
described in the attached table):
Binary Input (Object 1, Variations 1 and 2)
Binary Output (Object 10, Variation 2)
Analog Input (Object 30, Variations 1, 2, 3 and 4)
Analog Input Change (Object 32, Variations 1, 2, 3 and 4)
Warm Restart (Function code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Data Link Re-tries:
None
Fixed
Configurable (Note 1)
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable (Note 1)
Requires Application Layer Confirmation:
Never
Always
When reporting Event Data
When sending multi-fragment responses
Sometimes
Configurable
Timeouts while waiting for:
Data Link Confirm
Complete Appl. Fragment
Application Confirm
Complete Appl. Response
Others:
GE Multilin
Courtesy of NationalSwitchgear.com
None
Fixed
None
Fixed
None
Fixed
None
Fixed
(None)
750/760 Feeder Management Relay
7.5.1 DEVICE PROFILE DOCUMENT
Device Function:
Master
Slave
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Application Layer Re-tries:
None
Configurable
Variable
Configurable (Note 1)
Variable
Configurable
Variable
Configurable
Variable
Configurable
7.5 DNP COMMUNICATIONS
7-49