GE Feeder Management Relay 750 Instruction Manual page 34

Table of Contents

Advertisement

3.1 MECHANICAL
Table 3–1: REAR TERMINAL ASSIGNMENTS
TERMINAL DESCRIPTION
ANALOG INPUT / OUTPUTS
A1
ANALOG INPUT +
A2
ANALOG INPUT -
A3
SHIELD (GROUND)
A4
ANALOG OUTPUT -
A5
ANALOG OUTPUT 1 +
A6
ANALOG OUTPUT 2 +
A7
ANALOG OUTPUT 3 +
A8
ANALOG OUTPUT 4 +
A9
ANALOG OUTPUT 5 +
3
A10
ANALOG OUTPUT 6 +
A11
ANALOG OUTPUT 7 +
A12
ANALOG OUTPUT 8 +
COMMUNICATION
B1
COM1 RS485 +
B2
COM1 RS485 -
B3
COM1 RS485 COM
B4
COM1 RS422 TX +
B5
COM1 RS422 TX -
B6
COM2 RS485 +
B7
COM2 RS485 -
B8
COM2 RS485 COM
B9
SHIELD (GROUND)
B10
IRIG-B +
B11
IRIG-B -
B12
RESERVED
LOGIC INPUTS
C1
LOGIC INPUT 1
C2
LOGIC INPUT 2
C3
LOGIC INPUT 3
C4
LOGIC INPUT 4
C5
LOGIC INPUT 5
C6
LOGIC INPUT 6
C7
LOGIC INPUT 7
C8
RESERVED
C9
RESERVED
C10
SETPOINT ACCESS –
C11
SETPOINT ACCESS +
C12
+32 VDC
LOGIC INPUTS
D1
LOGIC INPUT 8
D2
LOGIC INPUT 9
D3
LOGIC INPUT 10
D4
LOGIC INPUT 11
D5
LOGIC INPUT 12
D6
LOGIC INPUT 13
D7
LOGIC INPUT 14
D8
RESERVED
D9
RESERVED
D10
RESERVED
D11
RESERVED
D12
DC NEGATIVE
3-6
Courtesy of NationalSwitchgear.com
TERMINAL DESCRIPTION
OUTPUT RELAYS
E1
SOLID STATE TRIP OUT +
E2
1 TRIP RELAY NO
E3
2 CLOSE RELAY NO
E4
3 AUXILIARY RELAY NO
E5
3 AUXILIARY RELAY NC
E6
4 AUXILIARY RELAY NC
E7
5 AUXILIARY RELAY NC
E8
5 AUXILIARY RELAY NO
E9
6 AUXILIARY RELAY NC
E10
7 AUXILIARY RELAY NC
E11
7 AUXILIARY RELAY NO
E12
8 SELF-TEST WARNING RELAY NC
OUTPUT RELAYS
F1
SOLID STATE TRIP OUT -
F2
1 TRIP RELAY COM
F3
2 CLOSE RELAY COM
F4
3 AUXILIARY RELAY COM
F5
4 AUXILIARY RELAY NO
F6
4 AUXILIARY RELAY COM
F7
5 AUXILIARY RELAY COM
F8
6 AUXILIARY RELAY NO
F9
6 AUXILIARY RELAY COM
F10
7 AUXILIARY RELAY COM
F11
8 SELF-TEST WARNING RELAY NO
F12
8 SELF-TEST WARNG RELAY COM
CT and VT INPUTS / GROUND
G1
COIL MONITOR 1 +
G2
COIL MONITOR 2 +
SENSITIVE GROUND CT ■
G3
G4
SYNCHRO VT ■ (LINE)
G5
PHASE A VT ■ (BUS)
G6
PHASE C VT ■ (BUS)
G7
PHASE A CT ■
PHASE B CT ■
G8
PHASE C CT ■
G9
GROUND CT ■
G10
G11
FILTER GROUND
G12
SAFETY GROUND
CT and VT INPUTS / POWER
H1
COIL MONITOR 1 -
H2
COIL MONITOR 2 -
H3
SENSITIVE GROUND CT
H4
SYNCHRO VT (LINE)
H5
PHASE B VT ■ (BUS)
H6
PHASE VT NEUTRAL (BUS)
H7
PHASE A CT
H8
PHASE B CT
H9
PHASE C CT
H10
GROUND CT
H11
CONTROL POWER -
H12
CONTROL POWER +
750/760 Feeder Management Relay
3 INSTALLATION
GE Multilin

Advertisement

Table of Contents
loading

This manual is also suitable for:

Feeder management relay 760

Table of Contents