5 SETPOINTS
PATH: SETPOINTS
S4 OUTPUT RELAYS

2 CLOSE RELAY

[ENTER] for more
A
TRIP RELAY SEAL IN TIME
thus extending its pulse width. This is for use in applications where the 52 contacts reporting breaker state to the 750/760
are faster than the 52 contacts that are responsible for interrupting coil current.
GE Multilin
Courtesy of NationalSwitchgear.com
2 CLOSE RELAY
ð
ENTER
TRIP RELAY SEAL IN
ESCAPE
TIME: 0.04 s
can be programmed for the Close Relay. This time is added to the reset time of the Close Relay,
Figure 5–2: OUTPUT RELAY 2 CLOSE LOGIC
750/760 Feeder Management Relay
5.5 S4 OUTPUT RELAYS
5.5.3 CLOSE RELAY
Range: 0.00 to 9.99 s in steps of 0.01
5
5-29