PATH: SETPOINTS
S6 MONITORING
PULSED OUTPUT
[ENTER] for more
The 750/760 can operate selected auxiliary relays after an adjustable interval for the quantities shown above. Pulses occur
at the end of each programmed interval. Upon power up of the relay the Pulse Output function, if enabled, will continue
from where it was at loss of control power. For example, if control power is removed when the positive watthours actual
value is 16.0 MWh, when control power is re-applied a pulse will occur at 26 MWh if the interval is set to 10.0 MWh.
Note that the Output relay(s) used for this element must be set to "Self-Resetting" under
consist of a one second on time and a one second off time. This feature should be programmed such that no more than one
pulse per two seconds will be required or the pulsing will lag behind the interval activation.
GE Multilin
Courtesy of NationalSwitchgear.com
PULSED OUTPUT
ð
ENTER
PULSED OUTPUT
ESCAPE
FUNCTION: Disabled
POS WATTHOURS PULSED
ESCAPE
MESSAGE
RELAYS (3-7): -----
POS WATTHOURS PULSED
ESCAPE
MESSAGE
INTERVAL:
10.0 MWh
NEG WATTHOURS PULSED
ESCAPE
MESSAGE
RELAYS (3-7): -----
NEG WATTHOURS PULSED
ESCAPE
MESSAGE
INTERVAL:
10.0 MWh
POS VARHOURS PULSED
ESCAPE
MESSAGE
RELAYS (3-7): -----
POS VARHOURS PULSED
ESCAPE
MESSAGE
INTERVAL:
10.0 Mvarh
NEG VARHOURS PULSED
ESCAPE
MESSAGE
RELAYS (3-7): -----
NEG VARHOURS PULSED
ESCAPE
MESSAGE
INTERVAL:
10.0 Mvarh
Figure 5–56: PULSED OUTPUT LOGIC
750/760 Feeder Management Relay
5.7 S6 MONITORING

5.7.9 PULSE OUTPUT

Range: Disabled, Alarm, Latched Alarm, Control
Range: Any combination of 3 to 7 Auxiliary relays
Range: 0.0 to 6553.5 MWh in steps of 0.1.
Quantities auto-range to appropriate units.
Range: Any combination of 3 to 7 Auxiliary relays
Range: 0.0 to 6553.5 MWh in steps of 0.1.
Quantities auto-range to appropriate units.
Range: Any combination of 3 to 7 Auxiliary relays
Range: 0.0 to 6553.5 Mvarh in steps of 0.1.
Quantities auto-range to appropriate units.
Range: Any combination of 3 to 7 Auxiliary relays
Range: 0.0 to 6553.5 Mvarh in steps of 0.1.
Quantities auto-range to appropriate units.
S4 OUTPUT RELAYS
5
. The pulses will
5-95