5 SETPOINTS
e) COIL MONITOR
PATH: SETPOINTS
S6 MONITORING
COIL MON 1
[ENTER] for more
Coil Monitor 1 and 2 are programmed in this subgroup. They are two identical elements that may be used to monitor trip or
close coils. The operation of this feature is described in Section 3.2.6: Trip/Close Coil Supervision on page 3–12.
Detection of a failed circuit regardless of the breaker state (i.e. detection of a failed trip circuit when the breaker is open)
requires
BRKR STATE BYPASS
detailed in Section 3.2.6: Trip/Close Coil Supervision on page 3–12.
GE Multilin
Courtesy of NationalSwitchgear.com
EQUIPMENT
COIL MON 1(2)
ð
COIL MON 1 NAME:
ENTER
ESCAPE
Trip Coil Monitor
COIL MON 1
ESCAPE
MESSAGE
FUNCTION: Disabled
COIL MON 1
ESCAPE
MESSAGE
RELAYS (3-7): -----
BRKR STATE
ESCAPE
MESSAGE
BYPASS: Disabled
COIL MON 1
ESCAPE
MESSAGE
DELAY: 5 s
COIL MON 1
ESCAPE
MESSAGE
TYPE: Trip
to be "Enabled". Generally, this selection will require a wiring modification of the breaker, as
Figure 5–54: COIL MONITOR LOGIC
750/760 Feeder Management Relay
5.7 S6 MONITORING
Range: Any combination of 18 alphanumeric characters.
Range: Disabled, Alarm, Latched Alarm, Control
Range: Any combination of 3 to 7 Auxiliary relays
Range: Enabled, Disabled
Range: 5 to 100 s in steps of 1
Range: Trip, Close
5
5-93