5.8 S7 CONTROL
c) AUTORECLOSE RATE SUPERVISION
PATH: SETPOINTS
S7 CONTROL
RATE SUPERVISION
[ENTER] for more
The autoreclose rate supervision feature monitors the number of recloses per hour. Once the number of recloses within
one hour exceeds the
5
d) AUTORECLOSE CURRENT SUPERVISION
PATH: SETPOINTS
S7 CONTROL
CURRENT SUPERVISION
[ENTER] for more
5-122
Courtesy of NationalSwitchgear.com
AR
RATE SUPERVISION
ð
RATE SUPERVISION
ENTER
ESCAPE
FUNCTION: Disabled
RATE SUPERVISION
ESCAPE
MESSAGE
RELAYS (3-7): -----
MAX AR
ESCAPE
MESSAGE
RATE: 25 /hr.
setpoint, the autoreclose scheme is sent to lockout.
MAX AR RATE
Figure 5–74: AUTORECLOSE RATE SUPERVISION LOGIC
AR
CURRENT SUPERVISION
ð
CURRENT SUPERVISION
ENTER
ESCAPE
FUNCTION: Disabled
3 SHOTS FOR CURRENT
ESCAPE
ABOVE: 17.00 x CT
MESSAGE
2 SHOTS FOR CURRENT
ESCAPE
ABOVE: 18.00 x CT
MESSAGE
1 SHOTS FOR CURRENT
ESCAPE
MESSAGE
ABOVE: 19.00 x CT
CURRENT SUPERVISION
ESCAPE
MESSAGE
TO LOCKOUT: Disabled
LOCKOUT FOR CURRENT
ESCAPE
MESSAGE
ABOVE: 20.00 x CT
750/760 Feeder Management Relay
Range: Disabled, Alarm, Latched Alarm, Control
Range: Any combination of the 3 to 7 Auxiliary relays
Range: 1 to 50/hr. in steps of 1
Range: Enabled, Disabled
Range: 0.00 to 20.00 x CT in steps of 0.01
Range: 0.00 to 20.00 x CT in steps of 0.01
Range: 0.00 to 20.00 x CT in steps of 0.01
Range: Enabled, Disabled
Range: 0.00 to 20.00 x CT in steps of 0.01