5.8 S7 CONTROL
5 SETPOINTS
For the
and
setpoints, enter the voltage magnitude as a fraction of the bus or
LIVE BUS MIN VOLTAGE
LIVE LINE MIN VOLTAGE
line VT input nominal voltage. If the bus or line voltage rises above the respective setting, the single bus or line voltage
input used for synchrocheck is established as "Live", or energized.
The voltage, angular, and frequency differences of the primary systems are also entered through the
MAX VOLTAGE DIFFER-
,
, and
setpoints, respectively. A voltage magnitude, angular, or fre-
ENCE
MAX ANGLE DIFFERENCE
MAX FREQ DIFFERENCE
quency differential on the two input voltages below the values entered here is within the permissible limit for synchronism.
5
Figure 5–60: SYNCHROCHECK LOGIC
5-100
750/760 Feeder Management Relay
GE Multilin
Courtesy of NationalSwitchgear.com