5 SETPOINTS
PATH: SETPOINTS
S3 LOGIC INPUTS

TRANSFER FUNCTIONS

[ENTER] for more
The following logic input functions are used exclusively for the bus transfer scheme. Refer to Section 5.8.7: Transfer on
page 5–107 for details on implementing the bus transfer scheme.
If the bus transfer feature is required, all logic input functions necessary for the operation of this scheme must be
assigned to contact inputs before any other functions. This is to ensure there are no conflicts.
NOTE
The
INCOMER 1(2) BRKR CLOSED
logic.
THE CLOSE FROM INCOMER 1(2)
The
TIE BRKR CONNECTED
to the load, such as when it is in the Test or Disconnected positions. The
state, for prevent-parallel or permission-to-transfer logic.
The
TRANSFORMER LOCKOUT
The
setpoint disables the transfer scheme.
BLOCK TRANSFER
GE Multilin
Courtesy of NationalSwitchgear.com
TRANSFER FUNCTIONS
ð
ENTER
SELECT TO TRIP:
ESCAPE
Disabled
UNDERVOLT ON OTHER
ESCAPE
MESSAGE
SOURCE: Disabled
INCOMER 1 BRKR
ESCAPE
MESSAGE
CLOSED: Disabled
INCOMER 2 BRKR
ESCAPE
MESSAGE
CLOSED: Disabled
TIE BRKR
ESCAPE
MESSAGE
CONNECTED: Disabled
TIE BRKR
ESCAPE
MESSAGE
CLOSED: Disabled
BLOCK TRANSFER:
ESCAPE
MESSAGE
Disabled
TRANSFORMER LOCKOUT:
ESCAPE
MESSAGE
Disabled
SOURCE TRIP:
ESCAPE
MESSAGE
Disabled
CLOSE FROM INCOMER1:
ESCAPE
MESSAGE
Disabled
CLOSE FROM INCOMER2:
ESCAPE
MESSAGE
Disabled
setpoints are used to track breaker state, for prevent-parallel or permission-to-transfer
setpoints signal the bus tie breaker to begin a close operation.
setpoint is used to inhibit transfers if the breaker cannot be used to pass current from the source
and
setpoints are used to initiate a transfer as Source 1(2) is about to be lost.
SOURCE TRIP
750/760 Feeder Management Relay
5.4 S3 LOGIC INPUTS
5.4.8 TRANSFER FUNCTIONS
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
Range: Input 1 to Input 20, Disabled
setpoint is used to track breaker
TIE BRKR CLOSED
5
5-25