5.6 S5 PROTECTION
e) NEGATIVE SEQUENCE VOLTAGE
PATH: SETPOINTS
S5 PROTECTION
NEG SEQ VOLTAGE
[ENTER] for more
To protect against loss of one or two source phases, or against a reversed phase sequence of voltage, the negative
sequence voltage element can be used to either cause a trip or generate an alarm when the negative sequence voltage
exceeds the specified threshold for a specified time delay.
5
5-62
Courtesy of NationalSwitchgear.com
NEGATIVE SEQUENCE
ð
NEG SEQ VOLTAGE
ENTER
ESCAPE
FUNCTION: Disabled
NEG SEQ VOLTAGE
ESCAPE
MESSAGE
RELAYS (3-7): -----
NEG SEQ VOLTAGE
ESCAPE
MESSAGE
PICKUP: 0.10 x VT
NEG SEQ VOLTAGE
ESCAPE
MESSAGE
DELAY: 2.0 s
Figure 5–26: NEGATIVE SEQUENCE VOLTAGE LOGIC
750/760 Feeder Management Relay
NEG SEQ VOLTAGE
Range: Disabled, Trip, Alarm, Latched Alarm, Control
Range: Any combination of 3 to 7 Auxiliary relays
Range: 0.00 to 1.25 x VT in steps of 0.01
Range: 0.0 to 6000.0 s in steps of 0.1
5 SETPOINTS