LCD Touchscreen Layout

The touchscreen serves as input and display. Touch the active portion of the display to execute a command.
12.1

Startup Display

The default opening screen for the UPS is the Main screen. The operator can begin operating the UPS immediately by
pressing the RUN key.
Only the Main and Settings tab screens allow operator input. The Monitor and Records display screens are read-only.
No data can be entered in these screens.
From the Main screen, the UPS can be placed On-Line by pressing RUN, or placed in Bypass Mode by pressing STOP. A
key status indicator at the upper right-hand corner of each key indicates which key is active: a dot indicates that key is ac-
tive; no dot indicates that key is not active. See the illustration below.
The Settings screen allows modification of the UPS operating parameters.
At the top of the display are four status indicators: % Load, Battery Information, UPS System Status, and System Time.
Security Level: USR
LCD TOUCHSCREEN
DISPLAY LAYOUT
At the top left of the display are a bank of four touch-sensitive keys:
Home – Pressing HOME key returns the display to the top menu of the currently selected tab.
Security Level – Pressing the Security Level key activates the log-in security screen.
(Speaker) – Pressing the Speaker key will disable/enable the audible alarm.
Touchscreen Lock – Locks touchscreen except for this key.
26
Battery Information
User
ADM
Administrator
% FullLoad
96%
HOME
Home Page
Main
Function Tabs
UPS Serial Number
20080112345
UPS Typeform
UXPB2B100C6
DVCOH
Fault Code
Warning Code
Speaker
On/Off
100%
INV
USR
Monitor
Settings
1600
XP
On-Line UPS
UPS Controls
RUN
STOP
ASYN
1600XPi Series UPS Installation and Operation Manual – 60616-014
Touchscreen lock
UPS System Status
12-Hour
12:35 PM
Clock
Records
Key Status Indicator
(UPS is in On-Line mode)
RUN key
Key Status Indicator
(UPS is NOT in Bypass
mode)
STOP key
UPS
On-Line
System
Mode

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents