Toshiba 1600XPi Series Installation And Operation Manual page 69

Single phase - 3.6/5.2/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

Display
Recorded
BOH
Y
BRPL
Y
BSDV
N
BTSTFL
N
BYPOV
N
BYPUV
N
CALL
Y
CHRGOV
Y
CLMT
N
DCER
Y
DCANERR
N
EXTBC1
N
EXTBC2
N
FBYPER
N
FIER
N
LB
N
1600XPi Series UPS Installation and Operation Manual – 60616-014
Meaning
Battery Overheat – Battery not
within specifications.
Replace Battery – Battery at end
of life expectancy.
Battery Shutdown Voltage – Bat-
tery is discharged down to mini-
mum level.
Battery Test Failed – Battery not
within specifications.
Bypass Overvoltage – Bypass
voltage exceeds UPS specifica-
tions.
Bypass Undervoltage – Bypass
voltage less than UPS specifica-
tions.
Service Call Required – Inspection
of the unit is advised.
Charger Overvoltage – Battery
Charger not within specifications.
Current Limit – UPS not within
specifications.
Display Cable Error – Display
cable is disconnected.
Communication Error between
Display and Main Controllers.
1.
BC1 Battery String 1, 2, or 3
Disconnected
2.
BC1 Over Temperature
3.
BC1 Lost Communications
with UPS
1.
BC2 Battery String 1, 2, or 3
Disconnected
2.
BC2 Over Temperature
3.
BC2 Lost Communications
with UPS
Bypass Frequency Error – Input
frequency outside of UPS specifi-
cations.
Input Frequency Error – Input
frequency outside of 45 – 65 Hz
range.
Low Battery – The battery level
has dropped low (about 90% or
less) during operation. Continued
operation in this mode will deplete
battery and cause output shut
down.
Action
Call Toshiba for service.
Replace battery immediately.
UPS will shut down. Secure critical loads until
power can be restored.
Call Toshiba for service.
UPS in Bypass Mode: UPS turns off bypass
power to the load until bypass power returns to
normal. Check bypass power.
UPS in Bypass Mode: UPS turns off bypass
power to the load until bypass power returns to
normal. Check bypass power.
Have inspection/service performed.
Call Toshiba for service.
Call Toshiba for service.
Connect the display cable.
Call Toshiba for service.
Recover without power cycle - Must Manually
Reset.
Reduce Load on BC, call factory Toshiba for
Service
Call Toshiba for Service
Recover without power cycle - Must Manually
Reset.
Reduce Load on BC, call Toshiba for Service
Call Toshiba for Service
UPS in Bypass Mode: UPS turns off bypass
power to the load until bypass frequency returns to
normal. Check bypass frequency.
UPS in On-Line Mode: UPS switches to BACKUP
mode until Input Frequency returns to normal.
Immediately shut down the load equipment in an
orderly fashion and then press the STOP key.
59