9.8

Battery Test

The 1600XPi allows the user to conduct automatic or manual battery tests as desired. The following steps detail the bat-
tery test procedures.
Automatic Battery Test:
The Automatic Battery Test Procedure is performed only if it is enabled during startup.
1.
Once the battery test is completed, Cmd 654 - Battery Test Condition Status is set to "Battery Test Prohibited". It
2.
will be re-enabled once timer Cmd 655 - Battery Test Frequency is reached.
Manual Battery Test:
The UPS must be in Online mode.
Change the security setting to "ADMIN".
1.
On the display, press the Monitor tab.
2.
On the display, press the C&C key.
3.
Use the Page (<< and >>) and Record (< and>) navigation keys to verify the following:
4.
a. Cmd 652 - Battery Test Startup must be set to "Disable"
b. Cmd 653 - Enable Battery Test set to "Enable" to allow the battery test to be performed.
c. Cmd 655 - Battery Test Frequency should be set to "0" (Daily Test)
d. Cmd 654 - Battery Test Condition Status should read "Enable - Battery Test OK
to perform"
NOTE: If Cmd 654 is "Disable", the user will have to power down and restart the unit to perform the battery
test.
e. Navigate to Cmd 609 - Requested State and press the "BattTest" button on the display.
If the test passes, the display returns to the Monitor screen.
If the test fails, the display returns to the Monitor screen and displays BTSTFL in the warning section at the bot-
tom left of the display, and the "Warning" LED blinks until the fault is cleared.
1600XPi Series UPS Installation and Operation Manual – 60616-014