9.8
Battery Test
The 1600XPi allows the user to conduct automatic or manual battery tests as desired. The following steps detail the bat-
tery test procedures.
Automatic Battery Test:
The Automatic Battery Test Procedure is performed only if it is enabled during startup.
1.
Once the battery test is completed, Cmd 654 - Battery Test Condition Status is set to "Battery Test Prohibited". It
2.
will be re-enabled once timer Cmd 655 - Battery Test Frequency is reached.
Manual Battery Test:
The UPS must be in Online mode.
Change the security setting to "ADMIN".
1.
On the display, press the Monitor tab.
2.
On the display, press the C&C key.
3.
Use the Page (<< and >>) and Record (< and>) navigation keys to verify the following:
4.
a. Cmd 652 - Battery Test Startup must be set to "Disable"
b. Cmd 653 - Enable Battery Test set to "Enable" to allow the battery test to be performed.
c. Cmd 655 - Battery Test Frequency should be set to "0" (Daily Test)
d. Cmd 654 - Battery Test Condition Status should read "Enable - Battery Test OK
to perform"
NOTE: If Cmd 654 is "Disable", the user will have to power down and restart the unit to perform the battery
test.
e. Navigate to Cmd 609 - Requested State and press the "BattTest" button on the display.
If the test passes, the display returns to the Monitor screen.
•
If the test fails, the display returns to the Monitor screen and displays BTSTFL in the warning section at the bot-
•
tom left of the display, and the "Warning" LED blinks until the fault is cleared.
1600XPi Series UPS Installation and Operation Manual – 60616-014
21