Toshiba 1600XPi Series Installation And Operation Manual page 85

Single phase - 3.6/5.2/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

Non–Standard Model: 5.2 kVA
Unit (Capacity)
General
Typeform
Certifications
Input Characteristics
Input Voltage
1
Input Frequency
Input Capacity
Input /(Max Input) Current @208V
Input/(Max. Input) Current @240V
Input Power Factor
Current THD (linear load)
Internal AC Input Breaker Rating
Battery Characteristics
Battery Type
Backup time, fully charged @ 0.7 power
factor, 77 °F
Backup time, fully charged @ 0.85 power
factor, 77 °F
Recharge Time
Battery Voltage (Nominal)
Output Characteristics
Output Voltage
Output Voltage Regulation
Output Frequency
AUTO/MAN Frequency
Voltage THD
Common-Mode Noise
Rated Load Power Factor
Efficiency (ac-dc-ac)
Voltage Transient
Voltage Transient Recovery
Rated Output Current (rms)
1.
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
3.
An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
4.
If Vin is below the minimum Vin window, the UPS goes to Battery Mode. If the UPS is in Fault and Vin is below the minimum
Vin window, the UPS goes to Bypass Mode
1600XPi Series UPS Installation and Operation Manual – 60616-014
±0.5 Hz/1.0 Hz/1.5 Hz (factory or authorized service center selectable only)
1
5.2 kVA (4.4 kW)
H3BG2L052C61T
UL 1778, CUL, RoHS Compliant
Single-phase, 208/240 Vac, +10%
45 – 65 Hz (auto-sensing)
0.98 Typical, 0.95 Minimum@ 100% Load
< 5% total harmonic distortion
Valve Regulated Lead Acid, Flame Retardant
24 hr. (full), 12 hr. (90%) for internal batteries only
Single-phase, 240/208/120 V
Factory or authorized service center selectable only
< 3% for linear load; < 6% for non-linear load
0.85 (0.6 – 1.0) lagging
< ±8% (Load of 0 – 100 %)
50 ms to within 2% of nominal
1
(to -30% at typical 70% load)
1,4
5.2 kVA
28.6 (30.3) A
24.8 (26.2) A
50 A/277 V
8 min.
2
7 min.
2
216 Vdc
= ± 3%
< 0.5 Vrms
≥83%
21 A
3
A7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents