Fan failure;
Cause
High internal ambient
Chopper malfunction
Inverter/chopper fault
temperature
Operation Mode After
Bypass operation – Chopper and inverter are stopped
Shutdown – No output
Fault
Inverter OL – Transfer to bypass
Audible Alarm
Yes – Continuous buzzer
Visible Alarm
Red Fault LED on
Fault relay closed
Relay Contact Alarm
Bypass relay closed
Auto-retransfer
No
56
1600XPi Series UPS Installation and Operation Manual – 60616-014