5.0
Operating the UPS
5.4

Front Panel Layout

5.5
UPS On-Line Mode Display
green
Normal
Overload
green
green
red
red
When output current is
between 30% and 100%,
the green lamps light in
15% increments (from
bottom to top) to indicate
relative output value
Battery
(This sample display
Backup
shows output current at
45% to 60% of rated
current).
All the green lamps will
light and the red Overload
lamp will flash. If the load
exceeds 135% of the max.
Battery
rated output the red
Overload lamp will light
Battery
continuously.Remove
Backup
overload as quickly as
possible to prevent fault
(fault timeouts vary
depending on overload
condition).
5 - 4
Low
During
TOSHIBA
During battery backup all
green lamps flash and the
red Backup lamp is lit
continuously. As the
batteries discharge, the
green lamps extinguish
from top to bottom to
indicate remaining battery
capacity (This sample
display shows battery
voltage between 75% and
90% of battery capacity).
All green lamps are off
and the red Backup lamp
is lit continuously or
flashing.