Toshiba 1600XPi Series Installation And Operation Manual page 23

Single phase - 3.6/5.2/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

Input and Jumper wire/bus strip connection for:
208 Vin – Using provided jumper, connect terminals 11 – 12.
1
2
L1
L2
208 Vin
240 Vin – Using provided jumper, connect terminals 13 – 12.
1
2
L1
L2
240 V
in
Output Cabling for:
120 Vout
Connect load across Terminals 4 – 6 or 6 – 7.
208 Vout
Connect load across terminals 5 – 7.
240 Vout
Connect load across terminals 4 – 7.
1600XPi Series UPS Installation and Operation Manual – 60616-014
Factory Installed N - G Jumper
3
4
5
6
G
X1
X2
N
32 V
88 V
120 V
120 V
208 V
240 V
Factory Installed N - G Jumper
3
4
5
6
G
X1
X2
N
32 V
88 V
120 V
120 V
208 V
240 V
12
7
8
11
X3
G
208
COM 240
Jumper
12
7
8
11
X3
G
208
COM 240
Jumper
3
4
G
X1
3
4
G
X1
3
4
G
X1
13
14
15
16
EPO1
EPO2
REMOTE1
NO
NO
EPO
Rmt Contacts
13
14
15
16
EPO1
EPO2
REMOTE1
NO
NO
EPO
Rmt Contacts
Factory Installed N - G Jumper
5
6
7
8
X2
N
X3
G
120 V
120 V
Factory Installed N - G Jumper
5
6
7
8
X2
N
X3
G
208 Vout
Factory Installed N - G Jumper
5
6
7
8
X2
N
X3
G
240 Vout
17
REMOTE2
17
REMOTE2
13