Operating the UPS

The 1600XPi should be installed by a certified electrician. Once installed, the 1600XPi is designed to be operated by any user. Anyone not familiar with
this UPS should read the manual before attempting to operate it.
10.1

Initial Startup (First Power-Up)

The first time the UPS is activated after being shipped from the factory, the following parameters need to be set by the
customer for site-specific ratings. Input Rated Voltage, Output Rated Voltage, UPS Date, and UPS Time. Review
Sections 13 and 14 before initializing the UPS.
1. Login to the UPS as ADMIN. See Section 14.3 detailed login directions.
2. The input frequency defaults to 60 Hz in, 60 Hz out. Change frequency values only if required.
3. The first screen displayed during the initial startup sequence requires the operator to select the nominal Input Voltage.
4. Select from 208V, 230V, or 240V, and press the Write key.
5. If the command has been accepted, the word "Successful" will appear at the bottom left side of the display.
6. Repeat the process in step 3 in selecting the Rated Output Voltage.
7. Use the keypad to type in the current date in the format: Day mm/dd/yyyy. (e.g. Mon 10/05/2009) and press Write.
8. Use the keypad to type in the current time in 12 hour format: hh:mm AM (e.g. 12:15 PM) and press Write.
9. The Main screen is now displayed. Verify the UPS is in BYPASS mode. The mode (lower right side of the display)
should display Bypass. If it does not display Bypass, press and momentarily hold the STOP button on the Main
display.
NOTE: The internal batteries recharge in both Bypass and On-Line modes. As soon as the input breaker is closed, the
internal batteries will begin recharging.
10. With the UPS in bypass mode, cycle power to the UPS as follows:
At the rear of the UPS switch the main circuit breaker MCCB to OFF.
Leave the UPS off until the DC bus is safely discharged (approximately 5 – 10 minutes).
Restart the UPS by switching the main circuit breaker ON.
The table below summarizes the initialization parameters:
ID
Command
111
Rated Vin
215
Rated Vout
634
UPS Date
635
UPS Time
11. After setup is completed, log back in as USER. See section 14.3 for guidance.
10.2

Battery Parameter Settings

Table 11-1 for setting the battery parameters during initial setup for these configurations: Stand-alone UPS; UPS + 1 Battery Cabinet; UPS + 2 Battery
Cabinets.
22
Select from 208V, 230V, or 240V, and press Write. (This parameter sets the multiplier for
the Over-/Under voltage detectors.)
Select from 208V, 230V, or 240V, and press Write. (This parameter sets the multiplier for
the Over-/Under voltage detectors.)
Input the date in this format: Mon 10/05/2009 and press Write.
Input the current time in 12 hour format: 12:15 PM and press Write.