5. Change the operating mode to Run App.
6. Press the Esc button repeatedly until the Full PV display appears.
Related information
Change the operating mode
Using the logging wizard for data logging of flow
measurements
The Logging Wizard is the easiest way to set-up the data logging feature after the main
application is set-up.
As an example, consider data logging of the control unit PV value (D800) every 15
minutes; the control unit PV is a flow measurement in cubic meters per second. When the
flow measurement is at 1 cubic meter per second or more, the Fast Log mode is required
to activate. When the memory is at 90% of capacity, a relay is activated instead of
overwriting old data.
Emerson.com/Rosemount
Figure 4-20: Logging Wizard Example with Data Logging of Level
Measurements
Logging Wizard
ESC =Quit
=Start
Set Interval
Set fast LOG trip
A
Overwrite old data
B
LOG Digital input(s)
C
A. Measurement units for this wizard are dependent on control unit PV display units
selected using P200.
B. Options: Yes, No
C. Options: None, 1, 2, Both
Key presses for the wizard example are provided alongside the prompts.
In the bottom-right of the display is now the word LOG, flashing to indicate that
data logging is operating.
15 min
0
000000 m
1
Yes
None
Getting started
January 2021
89