Emerson Rosemount 3490 Series Reference Manual page 105

4-20 ma + hart compatible controller
Hide thumbs Also See for Rosemount 3490 Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4841
Figure 4-30: Pump 1 and Pump 2 are Off (Level Okay)
E
A. Level in m
B. 8.0 m (P421)
C. 5.0 m (P411)
D. 2.0 m (P412)
E. Pump 1
F. Pump 2
When the level rises above 5 m (On point, P411), the relay RL1 is energized to start Pump 1
(Figure
Figure 4-31: Pump 1 is On (Rising Level Above 5 m)
E
A. Level in m
B. 8.0 m (P421)
C. 5.0 m (P411)
D. 2.0 m (P412)
E. Pump 1
F. Pump 2
If the level continues to rise and is above 8 m (On point, P421), the relay RL2 is energized
to start Pump 2. Relay RL1 is de-energized to switch off Pump 1
Emerson.com/Rosemount
A
B
C
D
F
4-31).
A
B
C
D
F
Getting started
January 2021
(Figure
4-32).
105

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3491Rosemount 3492Rosemount 3493

Table of Contents