Emerson Rosemount 3490 Series Reference Manual page 32

4-20 ma + hart compatible controller
Hide thumbs Also See for Rosemount 3490 Series:
Table of Contents

Advertisement

Installation
January 2021
Related information
Change the operating mode
Programming Channel 1 for a HART input (advanced users)
Programming Channel 2 for a HART input (Rosemount 3492 and advanced users only)
Display configuration options
3.4.7
Relay connections
Terminal connections are shown in
3.4.8
Current output connections
The Current Output may be connected in internally-powered or loop-powered mode, as
shown in
required. A minimum of 2.5 Vdc is required across terminals 7 and 8 for correct operation.
The voltage must not exceed 30 Vdc.
Figure 3-10: Internally-powered
A. Load
Figure 3-11: Loop-powered
A. Load
B. External supply
32
Figure 3-10
and
Figure
3-11. In loop-powered mode, an external power source is
24V
7
Io
+
8
A
-
0V
9
24V
7
Io
+
8
A
-
0V
9
Table 3-1
and
Table
3-2.
+
B
-
Reference Manual
00809-0100-4841
Emerson.com/Rosemount