Emerson Rosemount 3490 Series Reference Manual page 124

4-20 ma + hart compatible controller
Hide thumbs Also See for Rosemount 3490 Series:
Table of Contents

Advertisement

Getting started
January 2021
Table 4-31: Control Unit Reporting of Faults
Source
Cause
3490
Rom checksum error
RAM test error
Real Time Clock Fault
EEPROM Signature Error
EEPROM checksum error
ADC error
Control Unit temperature
out-of-limits
Xmtr
Field Device Malfunction
4.4.15
Set-up totalizing
The totalizer can be easily set-up using the Totalizer Wizard, accessible by navigating to
the TOTALIZER menu.
The Totalizer Wizard also forms a part of the Application (App) Wizard.
Note
The wizard requires the totalizer source parameter to have suitable units selected e.g.
3
m
/hour. If no suitable units are selected, an 'invalid units' message appears.
Procedure
Navigate to SETUP → CONTROLLER → OUTPUT → TOTALIZER → Totalizer Wizard.
Example
The Rosemount 3491 screens are shown here.
SETUP
Run App?
MONITOR
The SELECT INSTRUMENT menu does not appear unless a HART transmitter is connected.
After using a wizard, adjustments can be made to the totalizer parameters.
124
As seen on
Status
screen
LED
ROM Error
Constant
RAM Error
Constant
Clock fault
Constant
EEPROM Sig err
Constant
EEPROM CKS err
Constant
ADC_error
Constant
CU Temp OL
Constant
Xmtr Fault
Constant
MAIN MENU
SELECT INSTRUMENT
Controller: ****
1
Tx1: ****
APPLICATION
DISPLAY
OUTPUT
Full PV
Relay
Current
display
output
output
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
SETUP
OUTPUT
CURRENT OUTPUT
RELAY
TOTALIZER
1
Totalizer Wizard
Total Factor
Total Units
Reference Manual
00809-0100-4841
Alarm
Fault
report
report
(D830)
(D831)
N/A
Yes
N/A
Yes
N/A
Yes
N/A
Yes
N/A
Yes
N/A
Yes
N/A
Yes
N/A
Yes
TOTALIZER
Emerson.com/Rosemount

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3491Rosemount 3492Rosemount 3493

Table of Contents