Emerson Rosemount 3490 Series Reference Manual page 57

4-20 ma + hart compatible controller
Hide thumbs Also See for Rosemount 3490 Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4841
Figure 4-9: App Wizard Example: Tank Volume with High Alarm
Select Application
Esc =Back
A. Options: Level, Volume, Flow
B. Wait while transferring plot points
C. Options: Vertical cylinder, Horiz Cyl flat, Horiz Cyl domed, Rectangular, Spherical,
D. Options: Tank dimensions, Maximum volume
E. Options: Relay(s), Pump Control, Custom
F. Options: Relay 1, Relay 2, Relay 3, Relay 4
G. Options: Set point, Hi or Lo Alarm, Rate of change, Out of limits, Digital input
H. Exits to menu system. (Select Run App mode to start application.)
Emerson.com/Rosemount
App Wizard
Volume
=Next
Volume Wizard
C
Select Tank Shape
Horiz cyl flat
B
Choose method of
calibrating Tank
D
Tank dimensions
Enter value
of Tank diameter
6.5000 ft
Enter value
of Tank Length
255000 ft
.
Volume Wizard
max Tank Volume
6205.6 gal
Set Current Output ?
Enter volume
to give 4 mA out
0
000000 gal
Enter volume
to give 20 mA out
6200.0 gal
0
Set up Relays ?
Conical bottom, 20 point table
A
E
F
G
Getting started
January 2021
Relay Wizard
Select Function
Relay(s)
Relay(s)
Select Relay
Relay 1
Select Mode for
Relay 1
Hi or Lo Alarm
Enter On point
for Relay 1
006000 gal
Enter Off point
for Relay 1
005800 gal
Setup Complete
Program further
Esc
Relays?
H
57