Digital control voltage-free contact inputs
Allocate an action to IN1 or IN2
Procedure
1. Navigate to SETUP → [CONTROLLER] → DIGITAL INPUT → DIGITAL INPUT 1 or
2. Use the action selection parameter P340 (for IN1) or P345 (for IN2) to select a
3. Use the delay parameter P341 (for IN1) or P346 (for IN2) if a delay is needed before
84
DIGITAL INPUT 2.
trigger action from the option list.
Table 4-4
lists all the options and explains their purpose.
Table 4-4: Digital Input Actions
Action
Action that occurs while digital input is triggered
Free
Digital Input has no allocated action. This is the factory default
setting.
(1)
Alarm
Forces an alarm condition, which is indicated if specified in the
OUTPUT → ALARM menu.
(2)
Fault
Forces an fault condition, which is indicated if specified in the
OUTPUT → FAULT menu.
Program mode
Changes the control unit operating mode to Program (open
padlock).
Hold totalizer
Freezes the internal totalizer.
Hold MCU PV
Prevents the control unit PV value (D800) from being updated.
Suppress Alarm
If the digital input is active when an alarm condition is present, a
message is displayed indicating the alarm is being overridden.
Alarm relay is held on.
(3)
Display Msg
Displays a user-defined message (P241).
(4)
Log Input
When the next data logging interval elapses, flag the data logged as
a 'bad sample' if the digital input has been active.
(5)
Pump-down
Invoke a pump-down operation.
Lock Params
Prevent 'P' prefixed parameters from being edited.
Protect totalizer 1
Prevent totalizer 1 from being reset.
(6)
Reset totalizer 2
Reset totalizer 2.
(1)
See
Set-up
alarmsfor information about alarms and features they affect.
(2)
See
Fault mode relay
for how to indicate fault conditions using a relay output
(3)
SETUP → [CONTROLLER] → APPLICATION → Message.
(4)
Data logging is available on the Rosemount 3493.
(5)
The pump-down feature is available on the Rosemount 3491 and Rosemount 3492. See
Pump-down (Rosemount 3491 and 3492 only)
(6)
Totalizer 2 is available on the Rosemount 3492 and Rosemount 3493.
an action is performed. The setting format is m:s (minutes and seconds).
Reference Manual
00809-0100-4841
for further information.
Emerson.com/Rosemount

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3491Rosemount 3492Rosemount 3493

Table of Contents