A.3.6
Current output
Signal range (nominal)
4–20 mA
Output range (linear)
•
3.8 to 20.5 mA (user-selectable alarm current of 3.6, 21, or 22.5 mA) or
•
3.9 to 20.8 mA (user-selectable alarm current of 3.75 or 21.75 mA)
A.3.7
Load
R
is 2370 Ohms
max
A.3.8
Resolution
12-bit
A.3.9
Regulation
< 0.1% over load change from 0 to 600 Ohms
A.3.10
Isolation
Isolated from other terminals to 500 Vdc
A.3.11
Update rate (software)
Five times per second
A.3.12
Cable entry
IP-rated wall mount enclosure
Five positions pre-drilled, two glands and three blanking plugs supplied
NEMA-4X-rated wall mount enclosure
Positions require drilling by user, glands/conduits and blanking plugs are not supplied
Panel enclosure
Direct wiring to terminal blocks at rear
A.3.13
Cable connection
Wall mount enclosure
Cage clamp terminal blocks in separate terminal compartment