Outputs Fuel Valves V1 / V2 / V3 / Pv, Type Si - X8-02, X7-01, X7-02; Output Safety Valve Type Si - X6-03; Output For Indication Of Operation X8-04, Pin 2 - Siemens LMV27.100x2 Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Building Technologies
7.4.5 Outputs fuel valves V1 / V2 / V3 / PV, type SI – X8–02, X7-
01, X7-02
Protective earth (PE)
Auxiliary terminal V1 for series
connection of two AC 115 V valves
Fuel valve 1 (V1)
Figure 26: Output fuel valve V1 X8-02
Fuel valve 2 (V2)
Protective earth (PE)
Figure 27: Output fuel valve V2 X7-01
Fuel valve 3 (V3)/
Pilot valve (PV)
Protective earth (PE)
Figure 28: Output fuel valve V3 / pilot valve X7-02
Outputs for connection of the gas or oil valves, depending on the selected type of fuel
train (refer to chapter Sequence diagrams).
7.4.6
Output safety valve type SI – X6–03
Safety valve
Protective earth (PE)
Figure 29: Output safety valve X6-03
Output for connection of an oil valve or safety valve for liquefied gas. The output is
connected parallel to the output for the fan.
7.4.7

Output for indication of operation X8-04, pin 2

Indication of operation
Figure 30: Output for indication of operation X8-04
Output for connection of indication of operation.
Caution!
The output is connected parallel to the fuel valve V1.
Basic Documentation LMV27...
7 Basic unit LMV27
LMV...
Bild 286e/0409
LMV...
Bild 288e/0409
LMV...
Bild 290e/0812
LMV...
Bild 390e/1109
LMV...
Bild 294e/0409
47/219