Deleting Curves - Siemens LMV27.100x2 Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

control ¹)
25
Ho mod without
circulation
control ¹)
26
Ho 2 stage
without
circulation
control ¹)
27
Ho 3 stage
without
circulation
control ¹)
28
G mod mech
only air actuator
¹)
29
Gp2 mod mech
only air actuator
¹)
Building Technologies
Modulating
Heavy oil direct ignition, without circulation control, electronic modulating ratio
electronic
control.
2-stage
Heavy oil direct ignition, without circulation control, electronic 2-stage ratio
control.
3-stage
Heavy oil direct ignition, without circulation control, electronic 3-stage ratio
control.
Modulating
Gas direct ignition, only air actuator, mechanical modulating ratio control.
mechanical
Modulating
Gas pilot ignition 2, only air actuator, mechanical modulating ratio control.
mechanical
¹) Selected operating mode is not released for the LMV27.
With select: Error code 210 diagnostic code 0
(Also refer to chapter Fuel trains)

8.1 Deleting curves

To delete curves, the operating mode must be set to undefined «--». In that case, only
the fuel curves are deleted, the direction of rotation or the reference position of the
actuators is not changed.
Basic Documentation LMV27...
8 Selection of operating mode
Description
81/219
CC1P7541en
17.12.2018