Note
Ensure that the fuel train is correctly set in compliance with the type of burner used.
No.
201
Building Technologies
Parameter
Burner operating mode (fuel train, modulating / multistage,
actuators, etc.)
-- = undefined (delete curves)
1 = gas modulating (G mod)
2 = gas modulating with pilot valve 1 (Gp1 mod)
3 = gas modulating with pilot valve 2 (Gp2 mod)
4 = oil modulating (Lo mod)
5 = oil 2-stage (Lo 2 stage)
6 = oil 3-stage (Lo 3 stage)
7 = gas modulating pneumatic (G mod pneu)
8 = gas modulating pneumatic with pilot valve 1 (Gp1 mod
pneu)
9 = gas modulating pneumatic with pilot valve 2 (Gp2 mod
pneu)
10 = oil modulating with pilot valve (LoGp mod)
11 = oil 2-stage with pilot valve 2 (LoGp 2-stage)
12 = oil modulating with 2 fuel valves (Lo mod 2 fuel valves)
13 = oil modulating with pilot valve and 2 fuel valves (LoGp mod
2 fuel valves)
14 = gas modulating pneumatic without actuator (G mod pneu
without actuator, 0 active)
15 = gas modulating pneumatic with pilot valve 1 without
actuator (Gp1 mod pneu without actuator, 0 active)
16 = gas modulating pneumatic with pilot valve 2 without
actuator (Gp2 mod pneu without actuator, 0 active)
17 = oil 2-stage without actuator (Lo 2-stage without actuator, 0
active)
18 = oil 3-stage without actuator (Lo 3-stage without actuator, 0
active)
19 = gas modulating only gas actuator (G mod only gas
actuator, fuel active)
20 = gas modulating with pilot valve 1 only gas actuator (Gp1
mod only gas actuator, fuel active)
21 = gas modulating with pilot valve 2 only gas actuator (Gp2
mod only gas actuator, fuel active)
22 = oil modulating only oil actuator (Lo mod only oil actuator,
fuel active)
23 = heavy oil modulating with circulation control (Ho mod
separate circulation control
24 = heavy oil 2-stage with circulation control (Ho 2 stage
separate circulation control
25 = heavy oil modulation without circulation control (Ho mod
without circulation control)
26 = heavy oil 2-stage without circulation control (Ho 2 stage
without circulation control)
27 = heavy oil 3-stage without circulation control (Ho 3 stage
without circulation control)
28 = gas modulating mechanical only air actuator (G mod mech
only fuel active, fuel active)
29 = gas modulating mechanical with pilot valve 2 only air
actuator (Gp2 mod mech only air actuator, fuel active)
¹) Selected operating mode is not released for the LMV27.
With select: Error code 210 diagnostic code 0
Basic Documentation LMV27...
26 Parameter level
¹)
¹)
¹)
¹)
¹)
¹)
Actuator controlled
Air
●
●
●
●
●
●
●
●
●
●
●
●
●
●
---
---
---
---
---
---
---
---
---
●
●
●
●
●
●
●
¹)
CC1P7541en
17.12.2018
Fuel
●
●
●
●
●
---
---
---
---
---
●
---
●
●
---
---
---
---
---
●
●
●
●
●
---
●
---
---
---
---
159/219