Siemens LMV27.100x2 Basic Documentation page 184

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Par.
Parameter
no.
2...4 = 1...3 repetitions
Recharging time:
Entering into operation
Repetition limit air pressure failure
196
1 = no repetition
2 = 1 repetition
3 = 2 repetitions
Recharging time:
End of Shutdown phase
199
Repetition limit value actuators
1 = no repetition
2 = 1 repetition
3 = 2 repetitions
200
Basic unit LMV27
201
Burner operating mode (fuel train, modulating / multistage,
actuators, etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
184/219
Building Technologies
Number of
Type
Edit
elements
1
Std_u8
Edit
1
Std_u8
Edit
1
Selection
Edit / clear
Basic Documentation LMV27...
27 Parameter list
Value range
Increment
Min.
Max.
1
2
1
1
3
1
1
29
1
Default
Password level
setting
Write
Read
1
OEM
OEM
3
OEM
OEM
undefined
HF
HF (GA)
CC1P7541en
17.12.2018

Hide quick links:

Advertisement

Table of Contents
loading