26.11.9 Interpolation of curvepoints

Example 1 = gas modulating
P0, P1 and P9 are set as described:
P2 through P8 have automatically been
calculated:
P5 shall now be changed:
or
F
or
F
and
or
Building Technologies
P
V
h min s
P
V
h min s
P
A
V
h min s
A
P
V
h min s
Basic Documentation LMV27...
26 Parameter level
/reset
Identification of start for setting the curve
parameters.
%
Curvepoint
Value 1
fuel
P0
30.0
P1
32.0
P9
80.0
Curvepoint
Value 1
fuel
P2
38.0
P3
44.0
P4
50.0
P5
56.0
P6
62.0
P7
68.0
P8
74.0
/reset
%
Keep
or
F
Example:
F
%
Press
or
required.
Example: 50.0
%
Value 2
air
22.0
24.0
90.0
Value 2
air
32.3
40.5
48.8
57
65.3
73.5
81.8
depressed.
A
to change the value as
CC1P7541en
17.12.2018
171/219