Siemens LMV27.100x2 Basic Documentation page 207

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Error
Diagnostic code
code
251 (-5)
252 (-4)
253 (-3)
254 (-2)
255 (-1)
146
#
1
2
150
#
1 (-1)
2 (-2)
3 (-3)
4 (-4)
5 (-5)
154
#
1
2
155
#
1..9
21..29
41..49
61..69
156
#
Building Technologies
Meaning for the LMV27
Backup – burner identification is not defined
After restore, pages still on ABORT
Restore cannot at present be made
Abortion due to transmission error
Abortion due to timeout during restore
Timeout building automation interface
Modbus timeout
eBus timeout
TÜV test
Invalid phase
TÜV test default output too low
TÜV test default output too high
Manual abortion
TÜV test timeout
Trim function: Invalid analog value
Start prevention
Warning message (trim function temporarily deactivated)
Trim function: Invalid curve setting VSD / PWM fan
Minimum value VSD curve fall below
Maximum value VSD curve exceeded
Fuel 1: Minimum value VSD curve fall below
Fuel 1: Maximum value VSD curve exceeded
Trim function: Maximum time for range limit exceeded
Basic Documentation LMV27...
28 Error code list (of all LMV2 / LMV3 types)
Recommended measures or causes
Define burner identification and repeat backup
Repeat reset and backup
Repeat reset and backup
Repeat reset and backup
Make a reset, check the connections and repeat the backup
Refer to User Documentation Modbus (A7541)
TÜV test may only be started in phase 60 (operation)
TÜV test default output must be lower than the lower output limit
TÜV test default output must be higher than the upper output limit
No error: Manual abortion of TÜV test by the user
No loss of flame after fuel valves have been shut
1. Check for extraneous light
2. Check wiring for short-circuit
3. Check to see if one of the valves is leaking
1. Check wiring of analog trim specification to see if there is an open-circuit / loose contact
2. Check the process date of the read-in trim specification
(parameter 916; 4 mA = -15% / 12 mA = 0% / 20 mA = 15%)
The curve setting of the VSD / PWM fan must include a reserve for the set trim range.
((Minimum value curve + negative trim range)  curve point  (maximum value curve -
positive trim range))
The curvepoint of the VSD curve is below the permissible minimum value
(diagnostic code = curvepoint number; e.g. 1 = P1)
The curvepoint of the VSD curve is above the permissible maximum value
(diagnostic code = curvepoint number; e.g. 21 = P1)
Fuel 1: The curvepoint of the VSD curve is below the permissible minimum value
(diagnostic code = curvepoint number; e.g. 41 = P1)
Fuel 1: The curvepoint of the VSD curve is above the permissible maximum value
(diagnostic code = curvepoint number; e.g. 61 = P1)
Warning message!
Trim function is in limitation for too long (parameter 535; 916 < 531 or 916 >
532).This can be an indication that the trim function or the VSD curve is set
207/219
CC1P7541en
17.12.2018