Siemens LMV27.100x2 Basic Documentation page 188

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Par.
Parameter
no.
272
Oil: Interval 2
273
Oil: Afterburn time
274
Oil: Postpurge time
276
Oil: Input pressure switch-min
1 = active from phase 38
2 = active from safety time
277
Oil: Input pressure switch-max/POC
1 = pressure switch-max
2 = POC
3 = not used
4 = not used
280
Repetition limit value loss of flame
1 = no repetition
2 = 1 repetition
Recharging time:
After the Operation phase 1
Note!
Parameters 280 and 240 refer to the same value.
This means that no separate setting is possible for oil /
gas or fuel 0 / fuel 1.
281
Oil: Point in time oil is ignited
0 = short preignition (phase 38)
1 = long preignition (with fan) (phase 22)
284
Oil: Postpurge time (abortion with load controller-ON
288
Oil: Prepurge time (OEM)
400
Ratio control curves
401
Ratio control curve fuel actuator (only curve settings)
402
Ratio control curve air actuator (only curve settings)
500
Ratio control
501
No-flame positions fuel actuator
Index 0 = home position
188/219
Building Technologies
Number of
Type
Edit
elements
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Selection
Edit
1
Selection
Edit
1
Std_u8
Edit
1
Selection
Edit
1
Time
Edit
1
Time
Edit
13
Std_s16
Edit
13
Std_s16
Edit
3
Std_s16
Edit
Basic Documentation LMV27...
27 Parameter list
Value range
Increment
Min.
Max.
0,4 s
60 min
0,2 s
0,2 s
60 s
0,2 s
0,2 s
108 min
0,2 s
1
2
1
1
4
1
1
2
1
0
1
1
1 s
108 min
0,2 s
5 s
60 min
0,2 s
90°
0,1°
90°
0,1°
90°
0,1°
Default
Password level
setting
Write
Read
2 s
HF
HF
8 s
HF
HF
0,2 s
HF
HF
1
HF
HF
1
HF
HF
2
OEM
OEM
1
HF
HF
1 s
HF
HF
15 s
OEM
HF
0°; 0°; 15°;
HF
HF
undefined
0°; 90°; 45°;
HF
HF
undefined
Index
Value
HF
HF
0
CC1P7541en
17.12.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents