Siemens LMV27.100x2 Basic Documentation page 203

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Error
Diagnostic code
code
91
#
93
#
3
95
#
3 Ignition transformer
4 Fuel valve V1
5 Fuel valve V2
6 Fuel valve V3
96
#
3 Ignition transformer
4 Fuel valve V1
5 Fuel valve V2
6 Fuel valve V3
97
#
0
98
#
2 Safety valve
3 Ignition transformer
4 Fuel valve V1
5 Fuel valve V2
6 Fuel valve V3
99
#
3
100
#
105
#
0 Pressure switch min
Building Technologies
Meaning for the LMV27
Internal error LMV27
Error flame signal acquisition
Short-circuit of sensor
Error relay supervision
External power supply active contact
Error relay supervision
Relay contacts have welded
Error relay supervision
Safety relay contacts have welded or external power supply
fed to safety relay
Error relay supervision
Relay does not pull in
Internal error relay control
Internal error relay control
Internal error relay control
Internal error contact sampling
Stuck-At failure
Basic Documentation LMV27...
28 Error code list (of all LMV2 / LMV3 types)
Recommended measures or causes
Short-circuit at QRB
1. Check wiring.
2. Flame detector possibly faulty.
Check wiring
Test the contacts:
1. LMV27 connected to power: Fan output must be dead.
2. Disconnect power: Disconnect fan. No resistive connection between fan output and neutral
conductor allowed.
If one of the 2 tests fails, release the LMV27 since contact have definitively welded and safety can
no longer be ensured.
Test the contacts:
1. LMV27 connected to power: Fan output must be dead.
2. Disconnect power: Disconnect fan. No resistive connection between fan output and neutral
conductor allowed.
If one of the 2 tests fails, release the LMV27 since contacts have definitively welded and safety
can no longer be ensured.
Make a reset; if error occurs repeatedly, replace the LMV27
Make a reset; if error occurs repeatedly, replace the LMV27
Make a reset. If error occurs repeatedly, replace the LMV27
Software version V03.10: If error C:99 D:3 occurs during standardization of the VSD, deactivate
temporarily function Alarm in case of start prevention (parameter 210 = 0, when using a release
contact) or interrupt the load controller-ON signal
Make a reset; if error occurs repeatedly, replace the LMV27
Can be caused by capacitive loads or supply of DC voltage to the mains voltage inputs. The
203/219
CC1P7541en
17.12.2018