Panasonic S-160PE1R5B Technical Data & Service Manual page 98

Table of Contents

Advertisement

1
CHECKLIST AFTER INSTALLATION WORK
Work List
No.
Are the indoor units installed following the
Installation
1
content of the section "SELECTING THE
INSTALLATION SITE"? on page 1-11-2-1-1.
Is the earth leakage circuit breaker (all-pole
2
switching function provided) installed?
Is there any wrong installation of optional
3
parts or wrong wiring?
4
Was the ground wire work performed?
Are there any wrong power supply wiring,
5
wrong connection wire, wrong signal wire or
Tubing &
loose screw?
Wiring
Is the thickness of wire in accordance with
6
rule?
Is the power-supply voltage equal to the
7
nameplate of the unit?
Was the check of the airtight test, flared tube
8
fitting and gas leakage on the welded portion
performed?
Has the adhesive been applied to the drain
9
connecting portion (resin portion) of the
indoor unit?
Drain
10
Is there water leakage?
Check
Indoor unit drain pipe has a downward
11
gradient (1/100 or more) by rule. Is the drain
water flwing smoothly?
Was the heat insulation work at a
Heat
suitable location including the flared tube
12
Insulation
fittin(refrigerant tube & drain pipe) performed
properly?
13
Did the abnormal sound occur?
Test Run
Did the cool and warm airflow discharge
14
from the indoor unit?
Content
1-11-2-1-9
Possibility of Failure & Checkpoint
Check
There is a possibility of light injure or loss of
property.
Power failure or short circuit may cause electric
shock or fire. Check installation work and ground
wire work.
If the gas leakage occurs, the unit quality not
only becomes inferior but affects environment.
Repair it as quickly as possible.
The resin portion cracks after a few months and
it may cause water drain.
Since there is a possibility of water drain, repair
the drain pipe if the drain failure or water drain
occurs.
The quality of unit not only becomes inferior
but there is a possibility of the water drain. So,
perform the heat insulation work properly.
Check if there is a fan contact or distortion of
the indoor unit.
Check if the unit does not operate or there is a
wrong tubing or wiring connection with another
system.