Panasonic S-160PE1R5B Technical Data & Service Manual page 223

Table of Contents

Advertisement

Item code
Item
Ventilation fan operation
Wired remote controller
sensor
"Operation change control in
progress" display
OFF reminder function for
when weekly timer is used
Heat exchanger temperature
for cold air discharge
(Heat exchanger control
point for control to prevent
cold air)
Fan output switching
Fan tap setting
(External static pressure of
the rated air flow volume)
Repeat timer switching
Timer function change
prohibit
NOTE
Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
Do not change any setting data that does not appear in this list.
No.
None
0000
0001
Ventilation fan operated by remote controller.
0000
Not used. (Body sensor is used.)
Remote controller sensor is used.
0001
Normal (displayed)
0000
Not displayed
0001
0000
None
0001
Only stop time setting is enabled.
0013
Control temperature 13°C
0014
Control temperature 14°C
0025
Control temperature 25°C
0026
Control temperature 26°C
0000
Output linked with fan. (ON when indoor unit fan is operating.)
0001
Fan mode operation output
Type 180: 60Pa
0001
(Setting at shipment)
0002
Type 180: 100Pa
0003
Type 180: 150Pa
0000
Function disabled
0001
Function enabled
0000
Function disabled
0001
Function enabled
7-9
Setting data
Description
Type 200: 75Pa
Type 224: 75Pa
Type 200: 120Pa
Type 224: 130Pa
Type 200: 180Pa
Type 224: 200Pa
7