P15 Insufficient Gas Level Detected
1.
Abnormal Detection Method
Alarm occurs in the following cases:
Compressor's current value shows lower than a certain value.
Compressor's discharge temperature exceeds 95°C.
Electronic expansion valve is fully opened.
The difference between indoor unit heat exchanger temperature and intake temperature is less than 4K.
2.
Error Diagnosis
1 Adjustment
of
1-1
refrigerant
amount
1-2 Check leakage of refrigeration (leak test).
5
Insufficient gas level
(Check whether or not pressure level is normal.)
5-24
Recharge with
Yes
additional refrigerant.
No
1-2
Replace leaking part
Yes
with a new one.
No
See what happens.