Check of Density Limit
U-160PZH2R5
U-160PZH2R8, U-180PZH2R8, U-200PZH2R8, U-224PZH2R8
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for installation space of
appliance are determined according to the refrigerant charge amount [m
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
45.0
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
[m
] : The refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge amount in the field).
c
[m
] : Maximum refrigerant charge amount
max
U-160PZH2R5
U-180PZH2R8
U-160PZH2R8
m
5.20 kg
max
[m
] ≤ 1.22 : Can be installed
c
1.22 < [m
] ≤ [m
] : Installation possible with in the range of slanted line part
c
max
[m
] > [m
] : Can not be installed
c
max
Can be installed
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5
[m
] : the refrigerant charge
c
amount (kg)
1.22
• 5.20 indicates m
digit of the model U-160PZH2R5. U-160PZH2R8.
max
• 6.10 indicates m
digit of the model U-180PZH2R8.
max
• 7.60 indicates m
digit of the model U-200PZH2R8, U-224PZH2R8.
max
U-200PZH2R8
U-224PZH2R8
6.10 kg
7.60 kg
] used in the appliance.
c
* U-180PZH2R8
Can not be installed
* U-160PZH2R5, U-160PZH2R8
Can not be installed
Can not be installed
6.10
7.60
5.20
v