Panasonic S-160PE1R5B Technical Data & Service Manual page 105

Table of Contents

Advertisement

HOW TO INSTALL THE INDOOR UNIT
High Static Pressure Ducted Type
S-180PE3R5B, S-200PE3R5B, S-224PE3R5B
Required Minimum Space for Installation and Service
(1) Dimensions of suspension bolt pitch and unit
486
Drain port
Refrigerant
tubing joint
627 (Suspension bolt pitch)
Min. 916 (Space for service)
(2) Dimensions of indoor unit
4-37×12 hole
26-ø3.2 hole
486
1
2
7
1,006
554 (Suspension
bolt pitch)
Electrical
component
box
977
916
(63)
554
360
554
28-ø3.2 hole
(Suspension
bolt pitch)
627
(Suspension
Electrical component box
bolt pitch)
6
68
484
Inspection access (600×600) (Field supply)
Min. 690
(Space for service)
Ceiling
Min. 20
face
260
For communication
wiring port
Inspection access (600×600) (Field supply)
5
4
260
70
3
381
1-11-2-2-3
Unit: mm
Min. 150
70
For power supply
wiring port
Unit: mm
Refrigerant liquid tubing (Flare)
Type 180 : ø9.52
1
Type 200/224 : ø12.7
Refrigerant gas tubing (Brazing)
ø19.05
(Type 180 (Over 50 ~ 75 m) :
2
ø19.05 → ø25.4)
Reducer (field supply)
(Type 200/224 (Over 30 ~ 60 m) :
Connection tubing
ø19.05 → ø25.4)
3 Power supply port
4 Communication port
5 Drain port VP25
6 Air intake duct connecting side flange
7 Air discharge duct connecting side flange
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents