Panasonic S-160PE1R5B Technical Data & Service Manual page 110

Table of Contents

Advertisement

1
1-1. How to Set on PC Board
1. Turn off the power breaker to halt the supply of electricity to the PC board.
2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit control PCB is
placed. (Fig. 1-11-2-2-3)
3. Set the On/Off switches in the Off position which are now set in the On position.
Select the positions of the Select SW001 switches respectively to make the desired external static pressure settings referring to
the Table 1-11-2-2-2.
Table 1-11-2-2-2 External static pressure SW setting
External static pressure at the
time of rated airflow volume
180
200
150Pa
180Pa
100Pa
120Pa
60Pa
75Pa
1-2. Operating the Timer Remote Controller (CZ-RTC4)
How to set the external static pressure
1. Press and hold down the
simultaneously for 4 or more seconds. (
Unit No., Item Code and Detailed Data will blink on
the LCD display.)
2. The indoor unit numbers in the group control will be
sequentially displayed whenever the Unit Select button
is pressed
.
Only the fan motor for the selected indoor unit will operate
during this time.
3. Specify the "
buttons for the temperature setting buttons and confirm
the values. ("
4. Press the
/
values for the set data. See Table 1-11-2-2-3 and
Fig. 1-11-2-2-4 and select a value "
"
".
5. Press the
button.
The display will stop blinking and remain illuminated.
6. Press the
button. The fan motor will stop operating
and the LCD display will return to the normal stop mode.
SW001
224
TP6
TP3
ON
200Pa
1
2
ON
130Pa
1
2
75Pa
1
2
,
and
buttons
" item code by pressing the
" set at shipment)
buttons for the time to amend the
", "
SW001
TP1
ON
3
1
2
Setting at
3
shipment
ON
3
Table 1-11-2-2-3 Setting the external static pressure
, the
180
External static pressure of the rated
air flow volume
150 Pa
100 Pa
60 Pa
/
/
/
1
3
" or
NOTE:
Failure to set this parameter may result in
decreased airflow and condensation.
1-11-2-2-8
Indoor Unit control PC board
3
SW001
ON
1
2
3
Indoor unit
200
224
180 Pa
200 Pa
120 Pa
130 Pa
75 Pa
75 Pa
°
°
A
6
1
Fig. 1-11-2-2-3
Item code
1
4
1
4
2
5