Panasonic S-160PE1R5B Technical Data & Service Manual page 214

Table of Contents

Advertisement

Never use the DN code unlisted in the following table.
DN
05
Outdoor fan silent mode
07
Capacity matching ignored
0C
Indoor unit drain pump forced operation
Measures against smell when indoor unit cooling
0D
thermostat OFF
1A
Demand 1 current (%)
1B
Demand 2 current (%)
1D
Current control level
2B
DP operation time for slime measures
80
Refrigerant Type
Outdoor unit capacity
81
(Setting when the data is not stored in the EEPROM.
Do not change under normal conditions.)
6
Item
6-12
Setting No.
1=Silent mode 1 (P)
2=Silent mode 2,,,,,
0=Invalid (P)
0=Invalid
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
0=Invalid (P)
1=Measures against smell
0=0%
45=45%,,,,,
130=130%
0=0%
45=45%,,,,,
130=130%
0=40%
1=45%,,,,,
12=100%,,,,,
18=130,,,,,
19=-1(Invalid)(P)
20=20 minutes
40=40 minutes
60=60 minutes
(For details, see "5. Outdoor Unit CCU Control (4)")
410=R410A(P), 22=R22, 407=R407C, 32=R32
19=180 (Type 160)
0=Invalid
21=224 (Type 200)
(P) : Factory preset mode
3=Silent mode 3
1=Valid
40=40%
75=75% (P) ,,,,,
-1=No control
40=40%
50=50% (P) ,,,,,
-1=No control
16=120%,,,,,
30=30 minutes (P)
50=50 minutes
20=200 (Type 180)
22=250 (Type 224)